title: N2XSY
sku: N2XSY-medium-voltage-cables
description: >
Das N2XSY Kabel ist ein leistungsfähiges Mittelspannungskabel mit
Kupferleiter, VPE-Isolation und PVC-Mantel. Es bietet hervorragende
elektrische Eigenschaften und lässt sich auch bei komplexen Trassenführungen
sicher und effizient verlegen.
categories:
- Mittelspannungskabel
images:
- /uploads/2025/01/N2XSY-scaled.webp
application: >
Das N2XSY erfüllt die Normen DIN VDE 0276-620, HD 620 S2 und IEC 60502. Es ist
ausgelegt für die Verlegung in Innenräumen, Kabelkanälen, im Wasser, im Erdreich oder
im Freien (bei geschützter Installation). Ob in Industrieanlagen, Kraftwerken oder
Schaltanlagen dieses Kabel sorgt für eine sichere und verlustarme
Energieübertragung im Mittelspannungsbereich.
locale: de
---
<ProductTabs technicalData={<ProductTechnicalData data={{
"technicalItems": [
{
"label": "CPR class",
"value": "Eca",
"unit": ""
},
{
"label": "Maximal operating conductor temperature (°C)",
"value": "+90",
"unit": "°C"
},
{
"label": "Maximal short-circuit temperature (°C)",
"value": "+250",
"unit": "°C"
},
{
"label": "Minimal storage temperature (°C)",
"value": "-25",
"unit": "°C"
},
{
"label": "Minimal temperature for laying (°C)",
"value": "-5",
"unit": "°C"
},
{
"label": "Shape of conductor",
"value": "RM",
"unit": ""
},
{
"label": "Temperaturbereich (°C)",
"value": "-35-+90",
"unit": "°C"
}
],
"voltageTables": [
{
"voltageLabel": "6/10 kV",
"metaItems": [
{
"label": "Spannung",
"value": "6/10 kV"
},
{
"label": "Prüfspannung",
"value": "21",
"unit": "kV"
},
{
"label": "Temperaturbereich",
"value": "-35-+90",
"unit": "°C"
},
{
"label": "Leitertemperatur (max.)",
"value": "+90",
"unit": "°C"
},
{
"label": "Kurzschlusstemperatur (max.)",
"value": "+250",
"unit": "°C"
},
{
"label": "Minimale Verlegetemperatur",
"value": "-5",
"unit": "°C"
},
{
"label": "Minimale Lagertemperatur",
"value": "-25",
"unit": "°C"
},
{
"label": "CPR-Klasse",
"value": "Eca",
"unit": ""
},
{
"label": "Flammhemmend",
"value": "EN 60 332-1-2 / EN 60 332-1-3 / EN 60 332-1-4 / EN 60 332-1-5 / EN 60 332-1-6 / EN 60 332-1-7 / EN 60 332-1-8 / EN 60 332-1-9 / EN 60 332-1-10 / EN 60 332-1-11 / EN 60 332-1-12",
"unit": ""
}
],
"columns": [
{
"key": "Cond",
"label": "Leiter"
},
{
"key": "shape",
"label": "Form"
},
{
"key": "cap",
"label": "Cap [uF/km]"
},
{
"key": "DI",
"label": "DI [mm]"
},
{
"key": "RI",
"label": "RI [Ohm/km]"
},
{
"key": "Wi",
"label": "Wi [mm]"
},
{
"key": "Ibl",
"label": "Ibl [A]"
},
{
"key": "Ibe",
"label": "Ibe [A]"
},
{
"key": "Ik_cond",
"label": "Ik [kA]"
},
{
"key": "Wm",
"label": "Wm [mm]"
},
{
"key": "Rbv",
"label": "Rbv [mm]"
},
{
"key": "Ø",
"label": "Ø [mm]"
},
{
"key": "G",
"label": "G [kg/km]"
}
],
"rows": [
{
"configuration": "1x35/16",
"cells": [
"Cu",
"RM",
"0,22",
"15,3",
"0,524",
"3,4",
"197",
"187",
"5",
"2,1",
"360",
"24",
"904"
]
},
{
"configuration": "1x50/16",
"cells": [
"Cu",
"RM",
"0,24",
"16,3",
"0,387",
"3,4",
"238",
"220",
"7,1",
"2,1",
"390",
"26",
"1039"
]
},
{
"configuration": "1x70/16",
"cells": [
"Cu",
"RM",
"0,28",
"17,9",
"0,268",
"3,4",
"294",
"268",
"10",
"2,1",
"405",
"27",
"1271"
]
},
{
"configuration": "1x95/16",
"cells": [
"Cu",
"RM",
"0,3",
"19,4",
"0,193",
"3,4",
"358",
"320",
"13,6",
"2,1",
"435",
"29",
"1530"
]
},
{
"configuration": "1x120/16",
"cells": [
"Cu",
"RM",
"0,34",
"20,9",
"0,153",
"3,4",
"413",
"363",
"17,1",
"2,1",
"450",
"30",
"1809"
]
},
{
"configuration": "1x150/25",
"cells": [
"Cu",
"RM",
"0,36",
"22,3",
"0,124",
"3,4",
"468",
"405",
"21,4",
"2,1",
"480",
"32",
"2158"
]
},
{
"configuration": "1x185/25",
"cells": [
"Cu",
"RM",
"0,4",
"23,9",
"0,099",
"3,4",
"535",
"456",
"26,4",
"2,1",
"495",
"33",
"2524"
]
},
{
"configuration": "1x240/25",
"cells": [
"Cu",
"RM",
"0,44",
"26,4",
"0,075",
"3,4",
"631",
"526",
"34,3",
"2,1",
"540",
"36",
"3117"
]
},
{
"configuration": "1x300/25",
"cells": [
"Cu",
"RM",
"0,49",
"28,8",
"0,06",
"3,4",
"722",
"591",
"42,9",
"2,1",
"570",
"38",
"3786"
]
},
{
"configuration": "1x400/35",
"cells": [
"Cu",
"RM",
"0,54",
"31,4",
"0,047",
"3,4",
"827",
"662",
"57,2",
"2,1",
"615",
"41",
"4750"
]
},
{
"configuration": "1x500/35",
"cells": [
"Cu",
"RM",
"0,61",
"34,6",
"0,037",
"3,4",
"949",
"744",
"71,4",
"2,1",
"660",
"44",
"5786"
]
}
]
},
{
"voltageLabel": "12/20 kV",
"metaItems": [
{
"label": "Spannung",
"value": "12/20 kV"
},
{
"label": "Prüfspannung",
"value": "42",
"unit": "kV"
},
{
"label": "Temperaturbereich",
"value": "-35-+90",
"unit": "°C"
},
{
"label": "Leitertemperatur (max.)",
"value": "+90",
"unit": "°C"
},
{
"label": "Kurzschlusstemperatur (max.)",
"value": "+250",
"unit": "°C"
},
{
"label": "Minimale Verlegetemperatur",
"value": "-5",
"unit": "°C"
},
{
"label": "Minimale Lagertemperatur",
"value": "-25",
"unit": "°C"
},
{
"label": "CPR-Klasse",
"value": "Eca",
"unit": ""
},
{
"label": "Flammhemmend",
"value": "EN 60 332-1-2",
"unit": ""
}
],
"columns": [
{
"key": "Cond",
"label": "Leiter"
},
{
"key": "shape",
"label": "Form"
},
{
"key": "cap",
"label": "Cap [uF/km]"
},
{
"key": "DI",
"label": "DI [mm]"
},
{
"key": "RI",
"label": "RI [Ohm/km]"
},
{
"key": "Wi",
"label": "Wi [mm]"
},
{
"key": "Ibl",
"label": "Ibl [A]"
},
{
"key": "Ibe",
"label": "Ibe [A]"
},
{
"key": "Ik_cond",
"label": "Ik [kA]"
},
{
"key": "Wm",
"label": "Wm [mm]"
},
{
"key": "Rbv",
"label": "Rbv [mm]"
},
{
"key": "Ø",
"label": "Ø [mm]"
},
{
"key": "G",
"label": "G [kg/km]"
}
],
"rows": [
{
"configuration": "1x35/16",
"cells": [
"Cu",
"RM",
"0,16",
"19,5",
"0,524",
"5,5",
"200",
"189",
"5",
"2,1",
"435",
"29",
"1069"
]
},
{
"configuration": "1x50/16",
"cells": [
"Cu",
"RM",
"0,17",
"20,5",
"0,387",
"5,5",
"239",
"222",
"7,1",
"2,1",
"450",
"30",
"1203"
]
},
{
"configuration": "1x70/16",
"cells": [
"Cu",
"RM",
"0,19",
"22,1",
"0,268",
"5,5",
"297",
"271",
"10",
"2,1",
"465",
"31",
"1447"
]
},
{
"configuration": "1x95/16",
"cells": [
"Cu",
"RM",
"0,21",
"23,6",
"0,193",
"5,5",
"361",
"323",
"13,6",
"2,1",
"495",
"33",
"1718"
]
},
{
"configuration": "1x120/16",
"cells": [
"Cu",
"RM",
"0,23",
"25,1",
"0,153",
"5,5",
"416",
"367",
"17,1",
"2,1",
"510",
"34",
"2007"
]
},
{
"configuration": "1x150/25",
"cells": [
"Cu",
"RM",
"0,25",
"26,5",
"0,124",
"5,5",
"470",
"409",
"21,4",
"2,1",
"540",
"36",
"2364"
]
},
{
"configuration": "1x185/25",
"cells": [
"Cu",
"RM",
"0,27",
"28,1",
"0,099",
"5,5",
"538",
"461",
"26,4",
"2,1",
"555",
"37",
"2744"
]
},
{
"configuration": "1x240/25",
"cells": [
"Cu",
"RM",
"0,3",
"30,6",
"0,075",
"5,5",
"634",
"532",
"34,3",
"2,1",
"600",
"40",
"3352"
]
},
{
"configuration": "1x300/25",
"cells": [
"Cu",
"RM",
"0,35",
"33",
"0,06",
"5,5",
"724",
"599",
"42,9",
"2,1",
"630",
"42",
"4032"
]
},
{
"configuration": "1x400/35",
"cells": [
"Cu",
"RM",
"0,36",
"35,6",
"0,047",
"5,5",
"829",
"671",
"57,2",
"2,1",
"675",
"45",
"4988"
]
},
{
"configuration": "1x500/35",
"cells": [
"Cu",
"RM",
"0,43",
"38,8",
"0,037",
"5,5",
"953",
"754",
"71,4",
"2,1",
"720",
"48",
"6080"
]
}
]
},
{
"voltageLabel": "18/30 kV",
"metaItems": [
{
"label": "Spannung",
"value": "18/30 kV"
},
{
"label": "Prüfspannung",
"value": "63",
"unit": "kV"
},
{
"label": "Temperaturbereich",
"value": "-35-+90",
"unit": "°C"
},
{
"label": "Leitertemperatur (max.)",
"value": "+90",
"unit": "°C"
},
{
"label": "Kurzschlusstemperatur (max.)",
"value": "+250",
"unit": "°C"
},
{
"label": "Minimale Verlegetemperatur",
"value": "-5",
"unit": "°C"
},
{
"label": "Minimale Lagertemperatur",
"value": "-25",
"unit": "°C"
},
{
"label": "CPR-Klasse",
"value": "Eca",
"unit": ""
},
{
"label": "Flammhemmend",
"value": "EN 60 332-1-2",
"unit": ""
}
],
"columns": [
{
"key": "Cond",
"label": "Leiter"
},
{
"key": "shape",
"label": "Form"
},
{
"key": "cap",
"label": "Cap [uF/km]"
},
{
"key": "DI",
"label": "DI [mm]"
},
{
"key": "RI",
"label": "RI [Ohm/km]"
},
{
"key": "Wi",
"label": "Wi [mm]"
},
{
"key": "Ibl",
"label": "Ibl [A]"
},
{
"key": "Ibe",
"label": "Ibe [A]"
},
{
"key": "Ik_cond",
"label": "Ik [kA]"
},
{
"key": "Wm",
"label": "Wm [mm]"
},
{
"key": "Rbv",
"label": "Rbv [mm]"
},
{
"key": "Ø",
"label": "Ø [mm]"
},
{
"key": "G",
"label": "G [kg/km]"
}
],
"rows": [
{
"configuration": "1x50/16",
"cells": [
"Cu",
"RM",
"0,13",
"25,5",
"0,387",
"8",
"241",
"225",
"7,1",
"2,1",
"525",
"35",
"1439"
]
},
{
"configuration": "1x70/16",
"cells": [
"Cu",
"RM",
"0,15",
"27,1",
"0,268",
"8",
"299",
"274",
"10",
"2,1",
"540",
"36",
"1697"
]
},
{
"configuration": "1x95/16",
"cells": [
"Cu",
"RM",
"0,16",
"28,6",
"0,193",
"8",
"363",
"327",
"13,6",
"2,1",
"570",
"38",
"1979"
]
},
{
"configuration": "1x120/16",
"cells": [
"Cu",
"RM",
"0,17",
"30,1",
"0,153",
"8",
"418",
"371",
"17,1",
"2,1",
"585",
"39",
"2279"
]
},
{
"configuration": "1x150/25",
"cells": [
"Cu",
"RM",
"0,19",
"31,5",
"0,124",
"8",
"472",
"414",
"21,4",
"2,1",
"615",
"41",
"2648"
]
},
{
"configuration": "1x185/25",
"cells": [
"Cu",
"RM",
"0,2",
"33,1",
"0,099",
"8",
"539",
"466",
"26,4",
"2,1",
"630",
"42",
"3036"
]
},
{
"configuration": "1x240/25",
"cells": [
"Cu",
"RM",
"0,22",
"35,6",
"0,075",
"8",
"635",
"539",
"34,3",
"2,1",
"675",
"45",
"3661"
]
},
{
"configuration": "1x300/25",
"cells": [
"Cu",
"RM",
"0,24",
"38",
"0,06",
"8",
"725",
"606",
"42,9",
"2,1",
"705",
"47",
"4368"
]
},
{
"configuration": "1x400/35",
"cells": [
"Cu",
"RM",
"0,26",
"40,6",
"0,047",
"8",
"831",
"680",
"57,2",
"2,1",
"750",
"50",
"5347"
]
},
{
"configuration": "1x500/35",
"cells": [
"Cu",
"RM",
"0,29",
"43,8",
"0,037",
"8",
"953",
"765",
"71,4",
"2,4",
"795",
"53",
"6472"
]
}
]
}
]
}} />}>
<section>
<h3 data-start="435" data-end="481">Für kraftvolle Mittelspannungsanwendungen</h3>
<p data-start="483" data-end="868">Das <strong data-start="487" data-end="496">N2XSY</strong> erfüllt die Normen <strong data-start="516" data-end="536">DIN VDE 0276-620</strong>, <strong data-start="538" data-end="551">HD 620 S2</strong> und <strong data-start="556" data-end="569">IEC 60502</strong>. Es ist ausgelegt für die <strong data-start="596" data-end="708">Verlegung in Innenräumen, Kabelkanälen, im Wasser, im Erdreich oder im Freien (bei geschützter Installation)</strong>. Ob in <strong data-start="716" data-end="768">Industrieanlagen, Kraftwerken oder Schaltanlagen</strong> dieses Kabel sorgt für eine sichere und verlustarme Energieübertragung im Mittelspannungsbereich.</p>
<h3 data-start="870" data-end="905">Aufbau und technische Merkmale</h3>
<p data-start="907" data-end="1380">Das Kabel besteht aus einem <strong data-start="935" data-end="974">blanken, mehrdrähtigen Kupferleiter</strong> (Kl. 2), der von einer <strong data-start="998" data-end="1015">VPE-Isolation</strong> mit festhaftender <strong data-start="1034" data-end="1057">äußerer Leitschicht</strong> umgeben ist. Eine <strong data-start="1076" data-end="1101">leitfähige Bandierung</strong>, eine <strong data-start="1108" data-end="1160">Abschirmung aus Kupferdrähten mit Querleitwendel</strong>, zusätzliche Bandierung und ein <strong data-start="1193" data-end="1213">roter PVC-Mantel</strong> (Typ DMV6) runden den Aufbau ab. Die extrudierte Kombination von Isolierung und Leitschicht sorgt für einen <strong data-start="1322" data-end="1354">teilentladungsfreien Betrieb</strong> und hohe Zuverlässigkeit.</p>
<h3 data-start="1382" data-end="1420">Eigenschaften und Einsatzvorteile</h3>
<p data-start="1422" data-end="1807">Das N2XSY Kabel ist <strong data-start="1442" data-end="1458">erdverlegbar</strong>, <strong data-start="1460" data-end="1501">flammwidrig nach DIN VDE 0482-332-1-2</strong> und <strong data-start="1506" data-end="1555">frei von silikon- und cadmiumhaltigen Stoffen</strong>. Mit <strong data-start="1561" data-end="1590">+90°C Betriebstemperatur</strong> und <strong data-start="1595" data-end="1627">+250°C Kurzschlussresistenz</strong> eignet es sich ideal für Netze mit hoher thermischer Belastung. Die ausgezeichneten Verlegeeigenschaften ermöglichen auch bei schwieriger Streckenführung eine einfache Handhabung.</p>
</section>
</ProductTabs>