title: N2XSY
sku: N2XSY-medium-voltage-cables
description: >
The N2XSY cable is a high-performance medium-voltage cable with a copper
conductor, XLPE insulation, and a PVC sheath. It offers excellent electrical
characteristics and can be installed safely and efficiently, even in complex
routing situations.
categories:
- Medium Voltage Cables
images:
- /uploads/2025/01/N2XSY-scaled.webp
application: >
The N2XSY meets the standards DIN VDE 0276-620, HD 620 S2 and IEC 60502. It is designed
for installation indoors, in cable ducts, in water, underground, or outdoors (when
protected). Whether in industrial plants, power stations, or substations this cable
ensures safe and low-loss power transmission in medium-voltage networks.
locale: en
---
<ProductTabs technicalData={<ProductTechnicalData data={{
"technicalItems": [
{
"label": "CPR class",
"value": "Eca",
"unit": ""
},
{
"label": "Maximal operating conductor temperature (°C)",
"value": "+90",
"unit": "°C"
},
{
"label": "Maximal short-circuit temperature (°C)",
"value": "+250",
"unit": "°C"
},
{
"label": "Minimal storage temperature (°C)",
"value": "-25",
"unit": "°C"
},
{
"label": "Minimal temperature for laying (°C)",
"value": "-5",
"unit": "°C"
},
{
"label": "Operating temperature range (°C)",
"value": "-35-+90",
"unit": "°C"
},
{
"label": "Shape of conductor",
"value": "RM",
"unit": ""
}
],
"voltageTables": [
{
"voltageLabel": "6/10 kV",
"metaItems": [
{
"label": "Voltage",
"value": "6/10 kV"
},
{
"label": "Test voltage",
"value": "21",
"unit": "kV"
},
{
"label": "Operating temperature range",
"value": "-35-+90",
"unit": "°C"
},
{
"label": "Conductor temperature (max.)",
"value": "+90",
"unit": "°C"
},
{
"label": "Short-circuit temperature (max.)",
"value": "+250",
"unit": "°C"
},
{
"label": "Minimum laying temperature",
"value": "-5",
"unit": "°C"
},
{
"label": "Minimum storage temperature",
"value": "-25",
"unit": "°C"
},
{
"label": "CPR class",
"value": "Eca",
"unit": ""
},
{
"label": "Flame retardant",
"value": "EN 60 332-1-2 / EN 60 332-1-3 / EN 60 332-1-4 / EN 60 332-1-5 / EN 60 332-1-6 / EN 60 332-1-7 / EN 60 332-1-8 / EN 60 332-1-9 / EN 60 332-1-10 / EN 60 332-1-11 / EN 60 332-1-12",
"unit": ""
}
],
"columns": [
{
"key": "Cond",
"label": "Cond."
},
{
"key": "shape",
"label": "Shape"
},
{
"key": "cap",
"label": "Cap [uF/km]"
},
{
"key": "DI",
"label": "DI [mm]"
},
{
"key": "RI",
"label": "RI [Ohm/km]"
},
{
"key": "Wi",
"label": "Wi [mm]"
},
{
"key": "Ibl",
"label": "Ibl [A]"
},
{
"key": "Ibe",
"label": "Ibe [A]"
},
{
"key": "Ik_cond",
"label": "Ik [kA]"
},
{
"key": "Wm",
"label": "Wm [mm]"
},
{
"key": "Rbv",
"label": "Rbv [mm]"
},
{
"key": "Ø",
"label": "Ø [mm]"
},
{
"key": "G",
"label": "G [kg/km]"
}
],
"rows": [
{
"configuration": "1x35/16",
"cells": [
"Cu",
"RM",
"0.22",
"15.3",
"0.524",
"3.4",
"197",
"187",
"5",
"2.1",
"360",
"24",
"904"
]
},
{
"configuration": "1x50/16",
"cells": [
"Cu",
"RM",
"0.24",
"16.3",
"0.387",
"3.4",
"238",
"220",
"7.1",
"2.1",
"390",
"26",
"1039"
]
},
{
"configuration": "1x70/16",
"cells": [
"Cu",
"RM",
"0.28",
"17.9",
"0.268",
"3.4",
"294",
"268",
"10",
"2.1",
"405",
"27",
"1271"
]
},
{
"configuration": "1x95/16",
"cells": [
"Cu",
"RM",
"0.3",
"19.4",
"0.193",
"3.4",
"358",
"320",
"13.6",
"2.1",
"435",
"29",
"1530"
]
},
{
"configuration": "1x120/16",
"cells": [
"Cu",
"RM",
"0.34",
"20.9",
"0.153",
"3.4",
"413",
"363",
"17.1",
"2.1",
"450",
"30",
"1809"
]
},
{
"configuration": "1x150/25",
"cells": [
"Cu",
"RM",
"0.36",
"22.3",
"0.124",
"3.4",
"468",
"405",
"21.4",
"2.1",
"480",
"32",
"2158"
]
},
{
"configuration": "1x185/25",
"cells": [
"Cu",
"RM",
"0.4",
"23.9",
"0.099",
"3.4",
"535",
"456",
"26.4",
"2.1",
"495",
"33",
"2524"
]
},
{
"configuration": "1x240/25",
"cells": [
"Cu",
"RM",
"0.44",
"26.4",
"0.075",
"3.4",
"631",
"526",
"34.3",
"2.1",
"540",
"36",
"3117"
]
},
{
"configuration": "1x300/25",
"cells": [
"Cu",
"RM",
"0.49",
"28.8",
"0.06",
"3.4",
"722",
"591",
"42.9",
"2.1",
"570",
"38",
"3786"
]
},
{
"configuration": "1x400/35",
"cells": [
"Cu",
"RM",
"0.54",
"31.4",
"0.047",
"3.4",
"827",
"662",
"57.2",
"2.1",
"615",
"41",
"4750"
]
},
{
"configuration": "1x500/35",
"cells": [
"Cu",
"RM",
"0.61",
"34.6",
"0.037",
"3.4",
"949",
"744",
"71.4",
"2.1",
"660",
"44",
"5786"
]
}
]
},
{
"voltageLabel": "12/20 kV",
"metaItems": [
{
"label": "Voltage",
"value": "12/20 kV"
},
{
"label": "Test voltage",
"value": "42",
"unit": "kV"
},
{
"label": "Operating temperature range",
"value": "-35-+90",
"unit": "°C"
},
{
"label": "Conductor temperature (max.)",
"value": "+90",
"unit": "°C"
},
{
"label": "Short-circuit temperature (max.)",
"value": "+250",
"unit": "°C"
},
{
"label": "Minimum laying temperature",
"value": "-5",
"unit": "°C"
},
{
"label": "Minimum storage temperature",
"value": "-25",
"unit": "°C"
},
{
"label": "CPR class",
"value": "Eca",
"unit": ""
},
{
"label": "Flame retardant",
"value": "EN 60 332-1-2",
"unit": ""
}
],
"columns": [
{
"key": "Cond",
"label": "Cond."
},
{
"key": "shape",
"label": "Shape"
},
{
"key": "cap",
"label": "Cap [uF/km]"
},
{
"key": "DI",
"label": "DI [mm]"
},
{
"key": "RI",
"label": "RI [Ohm/km]"
},
{
"key": "Wi",
"label": "Wi [mm]"
},
{
"key": "Ibl",
"label": "Ibl [A]"
},
{
"key": "Ibe",
"label": "Ibe [A]"
},
{
"key": "Ik_cond",
"label": "Ik [kA]"
},
{
"key": "Wm",
"label": "Wm [mm]"
},
{
"key": "Rbv",
"label": "Rbv [mm]"
},
{
"key": "Ø",
"label": "Ø [mm]"
},
{
"key": "G",
"label": "G [kg/km]"
}
],
"rows": [
{
"configuration": "1x35/16",
"cells": [
"Cu",
"RM",
"0.16",
"19.5",
"0.524",
"5.5",
"200",
"189",
"5",
"2.1",
"435",
"29",
"1069"
]
},
{
"configuration": "1x50/16",
"cells": [
"Cu",
"RM",
"0.17",
"20.5",
"0.387",
"5.5",
"239",
"222",
"7.1",
"2.1",
"450",
"30",
"1203"
]
},
{
"configuration": "1x70/16",
"cells": [
"Cu",
"RM",
"0.19",
"22.1",
"0.268",
"5.5",
"297",
"271",
"10",
"2.1",
"465",
"31",
"1447"
]
},
{
"configuration": "1x95/16",
"cells": [
"Cu",
"RM",
"0.21",
"23.6",
"0.193",
"5.5",
"361",
"323",
"13.6",
"2.1",
"495",
"33",
"1718"
]
},
{
"configuration": "1x120/16",
"cells": [
"Cu",
"RM",
"0.23",
"25.1",
"0.153",
"5.5",
"416",
"367",
"17.1",
"2.1",
"510",
"34",
"2007"
]
},
{
"configuration": "1x150/25",
"cells": [
"Cu",
"RM",
"0.25",
"26.5",
"0.124",
"5.5",
"470",
"409",
"21.4",
"2.1",
"540",
"36",
"2364"
]
},
{
"configuration": "1x185/25",
"cells": [
"Cu",
"RM",
"0.27",
"28.1",
"0.099",
"5.5",
"538",
"461",
"26.4",
"2.1",
"555",
"37",
"2744"
]
},
{
"configuration": "1x240/25",
"cells": [
"Cu",
"RM",
"0.3",
"30.6",
"0.075",
"5.5",
"634",
"532",
"34.3",
"2.1",
"600",
"40",
"3352"
]
},
{
"configuration": "1x300/25",
"cells": [
"Cu",
"RM",
"0.35",
"33",
"0.06",
"5.5",
"724",
"599",
"42.9",
"2.1",
"630",
"42",
"4032"
]
},
{
"configuration": "1x400/35",
"cells": [
"Cu",
"RM",
"0.36",
"35.6",
"0.047",
"5.5",
"829",
"671",
"57.2",
"2.1",
"675",
"45",
"4988"
]
},
{
"configuration": "1x500/35",
"cells": [
"Cu",
"RM",
"0.43",
"38.8",
"0.037",
"5.5",
"953",
"754",
"71.4",
"2.1",
"720",
"48",
"6080"
]
}
]
},
{
"voltageLabel": "18/30 kV",
"metaItems": [
{
"label": "Voltage",
"value": "18/30 kV"
},
{
"label": "Test voltage",
"value": "63",
"unit": "kV"
},
{
"label": "Operating temperature range",
"value": "-35-+90",
"unit": "°C"
},
{
"label": "Conductor temperature (max.)",
"value": "+90",
"unit": "°C"
},
{
"label": "Short-circuit temperature (max.)",
"value": "+250",
"unit": "°C"
},
{
"label": "Minimum laying temperature",
"value": "-5",
"unit": "°C"
},
{
"label": "Minimum storage temperature",
"value": "-25",
"unit": "°C"
},
{
"label": "CPR class",
"value": "Eca",
"unit": ""
},
{
"label": "Flame retardant",
"value": "EN 60 332-1-2",
"unit": ""
}
],
"columns": [
{
"key": "Cond",
"label": "Cond."
},
{
"key": "shape",
"label": "Shape"
},
{
"key": "cap",
"label": "Cap [uF/km]"
},
{
"key": "DI",
"label": "DI [mm]"
},
{
"key": "RI",
"label": "RI [Ohm/km]"
},
{
"key": "Wi",
"label": "Wi [mm]"
},
{
"key": "Ibl",
"label": "Ibl [A]"
},
{
"key": "Ibe",
"label": "Ibe [A]"
},
{
"key": "Ik_cond",
"label": "Ik [kA]"
},
{
"key": "Wm",
"label": "Wm [mm]"
},
{
"key": "Rbv",
"label": "Rbv [mm]"
},
{
"key": "Ø",
"label": "Ø [mm]"
},
{
"key": "G",
"label": "G [kg/km]"
}
],
"rows": [
{
"configuration": "1x50/16",
"cells": [
"Cu",
"RM",
"0.13",
"25.5",
"0.387",
"8",
"241",
"225",
"7.1",
"2.1",
"525",
"35",
"1439"
]
},
{
"configuration": "1x70/16",
"cells": [
"Cu",
"RM",
"0.15",
"27.1",
"0.268",
"8",
"299",
"274",
"10",
"2.1",
"540",
"36",
"1697"
]
},
{
"configuration": "1x95/16",
"cells": [
"Cu",
"RM",
"0.16",
"28.6",
"0.193",
"8",
"363",
"327",
"13.6",
"2.1",
"570",
"38",
"1979"
]
},
{
"configuration": "1x120/16",
"cells": [
"Cu",
"RM",
"0.17",
"30.1",
"0.153",
"8",
"418",
"371",
"17.1",
"2.1",
"585",
"39",
"2279"
]
},
{
"configuration": "1x150/25",
"cells": [
"Cu",
"RM",
"0.19",
"31.5",
"0.124",
"8",
"472",
"414",
"21.4",
"2.1",
"615",
"41",
"2648"
]
},
{
"configuration": "1x185/25",
"cells": [
"Cu",
"RM",
"0.2",
"33.1",
"0.099",
"8",
"539",
"466",
"26.4",
"2.1",
"630",
"42",
"3036"
]
},
{
"configuration": "1x240/25",
"cells": [
"Cu",
"RM",
"0.22",
"35.6",
"0.075",
"8",
"635",
"539",
"34.3",
"2.1",
"675",
"45",
"3661"
]
},
{
"configuration": "1x300/25",
"cells": [
"Cu",
"RM",
"0.24",
"38",
"0.06",
"8",
"725",
"606",
"42.9",
"2.1",
"705",
"47",
"4368"
]
},
{
"configuration": "1x400/35",
"cells": [
"Cu",
"RM",
"0.26",
"40.6",
"0.047",
"8",
"831",
"680",
"57.2",
"2.1",
"750",
"50",
"5347"
]
},
{
"configuration": "1x500/35",
"cells": [
"Cu",
"RM",
"0.29",
"43.8",
"0.037",
"8",
"953",
"765",
"71.4",
"2.4",
"795",
"53",
"6472"
]
}
]
}
]
}} />}>
<section>
<h3 data-start="435" data-end="481">For powerful medium-voltage applications</h3>
<p data-start="483" data-end="868">The <strong data-start="487" data-end="496">N2XSY</strong> meets the standards <strong data-start="516" data-end="536">DIN VDE 0276-620</strong>, <strong data-start="538" data-end="551">HD 620 S2</strong> and <strong data-start="556" data-end="569">IEC 60502</strong>. It is designed for <strong data-start="596" data-end="708">installation indoors, in cable ducts, in water, underground, or outdoors (when protected)</strong>. Whether in <strong data-start="716" data-end="768">industrial plants, power stations, or substations</strong> this cable ensures safe and low-loss power transmission in medium-voltage networks.</p>
<h3 data-start="870" data-end="905">Construction and technical features</h3>
<p data-start="907" data-end="1380">The cable consists of a <strong data-start="935" data-end="974">bare, multi-stranded copper conductor</strong> (Class 2), surrounded by <strong data-start="998" data-end="1015">XLPE insulation</strong> with a tightly bonded <strong data-start="1034" data-end="1057">outer conductive layer</strong>. A <strong data-start="1076" data-end="1101">conductive tape</strong>, a <strong data-start="1108" data-end="1160">copper wire screen with counter helix</strong>, additional tape, and a <strong data-start="1193" data-end="1213">red PVC sheath</strong> (Type DMV6) complete the construction. The extruded combination of insulation and conductive layer ensures <strong data-start="1322" data-end="1354">partial discharge-free operation</strong> and high reliability.</p>
<h3 data-start="1382" data-end="1420">Properties and application benefits</h3>
<p data-start="1422" data-end="1807">The N2XSY cable is <strong data-start="1442" data-end="1458">suitable for underground installation</strong>, <strong data-start="1460" data-end="1501">flame-retardant according to DIN VDE 0482-332-1-2</strong>, and <strong data-start="1506" data-end="1555">free from silicone and cadmium-containing substances</strong>. With a <strong data-start="1561" data-end="1590">+90°C operating temperature</strong> and <strong data-start="1595" data-end="1627">+250°C short-circuit resistance</strong>, it is ideal for networks with high thermal loads. Excellent installation properties also allow for easy handling, even in complex routing scenarios.</p>
</section>
</ProductTabs>