Files
klz-cables.com/data/products/de/hochspannungskabel/na2xfk2y.mdx
Marc Mintel f7aa880d9f
Some checks failed
Build & Deploy / 🔍 Prepare (push) Successful in 1m19s
Build & Deploy / 🧪 QA (push) Failing after 3m32s
Build & Deploy / 🚀 Deploy (push) Has been skipped
Build & Deploy / 🏗️ Build (push) Failing after 7m51s
Build & Deploy / ⚡ Lighthouse (push) Has been skipped
Build & Deploy / 🧪 Smoke Test (push) Has been skipped
Build & Deploy / ♿ WCAG (push) Has been skipped
Build & Deploy / 🛡️ Quality Gates (push) Has been skipped
Build & Deploy / 🔔 Notify (push) Successful in 10s
feat: migration von directus zu payloadcms
2026-02-24 19:25:43 +01:00

268 lines
6.5 KiB
Plaintext
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
---
title: NA2X(F)K2Y
sku: NA2X(F)K2Y-high-voltage-cables
description: >
Die NA2X(F)K2Y-Hochspannungskabelserie ist für Spannungsklassen von 64/110kV
konzipiert und verwendet hochleitfähige Kupferleiter, ideal für industrielle
Anwendungen, die hohe Strombelastbarkeit und ausgezeichnete
Durchschlagsfestigkeit erfordern.
categories:
- Hochspannungskabel
images: []
application: >
Die NA2X(F)K2Y-Hochspannungskabelserie ist speziell für den Einsatz in
Hochspannungsanwendungen entwickelt worden, wobei sie sich durch eine hohe
Strombelastbarkeit und exzellente Kurzschlussstromfestigkeit auszeichnet. Diese Kabel
sind mit einer fortschrittlichen XLPE-Isolierung ausgestattet, die eine hohe
Durchschlagsfestigkeit and Thermozyklierungsfähigkeit bietet.
locale: de
---
<ProductTabs technicalData={<ProductTechnicalData data={{
"technicalItems": [
{
"label": "Nennspannung (kV)",
"value": "64/110",
"unit": "kV"
}
],
"voltageTables": [
{
"voltageLabel": "64/110 kV",
"metaItems": [
{
"label": "Spannung",
"value": "64/110 kV"
}
],
"columns": [
{
"key": "Cond",
"label": "Leiter"
},
{
"key": "RI",
"label": "RI [Ohm/km]"
},
{
"key": "Wi",
"label": "Wi [mm]"
},
{
"key": "Rbv",
"label": "Rbv [mm]"
},
{
"key": "Ø",
"label": "Ø [mm]"
},
{
"key": "G",
"label": "G [kg/km]"
}
],
"rows": [
{
"configuration": "1×150RM",
"cells": [
"Al",
"0,26",
"18",
"1,3",
"67",
"7360"
]
},
{
"configuration": "1×185RM",
"cells": [
"Al",
"0,21",
"17",
"1,3",
"66",
"7270"
]
},
{
"configuration": "1×240RM",
"cells": [
"Al",
"0,16",
"16,5",
"1,3",
"67",
"7480"
]
},
{
"configuration": "1×300RM",
"cells": [
"Al",
"0,13",
"15,5",
"1,3",
"67",
"7600"
]
},
{
"configuration": "1×400RM",
"cells": [
"Al",
"0,1",
"14,5",
"1,4",
"68",
"7890"
]
},
{
"configuration": "1×500RM",
"cells": [
"Al",
"0,08",
"14",
"1,4",
"70",
"8400"
]
},
{
"configuration": "1×630RM",
"cells": [
"Al",
"0,06",
"14",
"1,5",
"74",
"9390"
]
},
{
"configuration": "1×800RM",
"cells": [
"Al",
"0,05",
"14",
"1,6",
"78",
"10350"
]
},
{
"configuration": "1×1000RM",
"cells": [
"Al",
"0,04",
"14",
"1,7",
"84",
"11620"
]
},
{
"configuration": "1×1200RMS",
"cells": [
"Al",
"0,03",
"14",
"1,8",
"91",
"13250"
]
},
{
"configuration": "1×1400RMS",
"cells": [
"Al",
"0,03",
"14",
"1,9",
"93",
"14100"
]
},
{
"configuration": "1×1600RMS",
"cells": [
"Al",
"0,02",
"14",
"1,9",
"97",
"15160"
]
},
{
"configuration": "1×1800RMS",
"cells": [
"Al",
"0,02",
"14",
"2",
"101",
"16410"
]
},
{
"configuration": "1×2000RMS",
"cells": [
"Al",
"0,02",
"14",
"2,1",
"103",
"17160"
]
},
{
"configuration": "1×2500RMS",
"cells": [
"Al",
"0,02",
"14,5",
"2,2",
"110",
"19420"
]
},
{
"configuration": "1×3000RMS",
"cells": [
"Al",
"0,01",
"14,5",
"2,4",
"119",
"22550"
]
}
]
}
]
}} />}>
<h2>Technische Übersicht</h2>
<p>Die <strong>NA2X(F)K2Y-Hochspannungskabelserie</strong> ist speziell für den Einsatz in Hochspannungsanwendungen entwickelt worden, wobei sie sich durch eine hohe Strombelastbarkeit und exzellente Kurzschlussstromfestigkeit auszeichnet. Diese Kabel sind mit einer fortschrittlichen XLPE-Isolierung ausgestattet, die eine hohe Durchschlagsfestigkeit und Thermozyklierungsfähigkeit bietet.</p>
<h2>Installations- und Konstruktionsmerkmale</h2>
<p>Die NA2X(F)K2Y-Kabel sind für verschiedene Verlegeverfahren wie Erdverlegung, Kabeltrassen-Montage und Kleeblattformation geeignet. Diese Flexibilität in der Installation macht sie zu einer bevorzugten Wahl für vielfältige industrielle Anwendungen.</p>
<ul>
<li>Verwendung von hochleitfähigem Kupfer als Leitermaterial für optimale Leitfähigkeit und Effizienz.</li>
<li>XLPE-Isolierung gewährleistet eine verbesserte thermische Beständigkeit und Langlebigkeit unter extremen Betriebsbedingungen.</li>
<li>Die Kabelkonstruktion unterstützt die Einhaltung der EMV-Anforderungen und minimiert die Risiken der Spannungsinduzierung.</li>
</ul>
<h2>Normen und Zertifizierungen</h2>
<p>Die Einhaltung internationaler und regionaler Normen ist für die NA2X(F)K2Y-Kabelserie von entscheidender Bedeutung. Diese Produkte sind vollständig IEC-konform und tragen die CE-Kennzeichnung, was ihre Qualität und Sicherheit in verschiedenen Anwendungsbereichen bestätigt.</p>
<ul>
<li>CPR-Klassifizierung sorgt für die Einhaltung strenger europäischer Sicherheitsstandards.</li>
<li>Die Kabelserie erfüllt die Anforderungen für hohe Spannungsklassen und bietet zuverlässige Leistung in anspruchsvollen Umgebungen.</li>
</ul>